banner
News center
Factory pricing with exceptional quality

The Importance Of Filter

Aug 24, 2023

The word desiccate means to dry out completely and a desiccant is a material or substance that accomplishes the moisture removal. Moisture in the mechanical refrigeration cycle is detrimental to the operation and life of the system. The filter-drier is an accessory that performs the functions of filtering out particles and removing and holding moisture to prevent it from circulating through the system.

Some combinations of atomic elements create molecular structures that can be either useful or harmful. Acids are formed when the right combination of elements are linked together chemically. If we have a use for the acid and use it for its intended purpose, all is well. However, in some cases unwanted chemical combinations occur where we least want them and where they cause serious harm. Under certain circumstances, hydrochloric and hydrofluoric acids chemically form in the mechanical refrigerant system. This, of course, is what we want to prevent.

Again, let us consider how the chemist facilitates the chemical bonding process. The chemist wants certain chemical reactions to take place in an effort to create new substances that hopefully have special properties that are useful. Perhaps the chemist is attempting to create a new refrigerant to replace another that is being phased out. The chemist combines particular elements to form bonds or links that when complete meet all the qualities of a suitable refrigerant. A catalyst is anything that hastens, encourages, or helps bring about a result. Heat is one of chemistry’s most active catalysts. A chemist may purposely add heat to a beaker of chemicals to cause them to combine to form a new substance.

The system contains components which consist of a number of metals such as the iron casting of the compressor, copper lines, steel condenser, aluminum evaporator, brass valves and fittings, and perhaps still other metals in smaller quantities. The components are assembled using still other metals and chemicals during the brazing process. Flux is applied to facilitate the chemical process of brazing, and heat is applied with a torch as the catalyst.

Still other materials (chemicals) are contained in the system. Compressor motor winding insulation and varnishes, epoxy glues, and perhaps rubber and gasket materials are applied. Of course, two of the major chemical materials that constantly circulate through the system are the refrigerant and oil.

The system contains a vast number of chemicals. (Everything physical is chemical and consists of atoms capable of bonding with atoms of other elements under the right circumstances.) Now, if yet additional elements are introduced to the existing combination of elements making up the system, the chemical bonding possibilities become still greater. During the installation or servicing of the system, air consisting of hydrogen, nitrogen, and oxygen may be introduced. Moisture may be introduced and flux or even powder from the inside of insulation may get into the system. The moisture and oxygen are very active components that act as catalysts themselves.

Additional catalysts in the form of heat or compression, as well as latent heat in the condenser and pressure are present. Imagine the possibilities. The chemicals present are compressed, heated, and liquefied. Then they are evaporated and cooled as the pressure is released. Then the process is continually repeated for hours, days, and months until a chemical reaction takes place. On hot days, the high temperature and pressure on the high side of the system reaches still higher levels. The catalysts of heat and pressure could almost make a chemist jealous.

When a chemical reaction occurs, the typical chemical bonding creates hydrochloric and hydrofluoric acids. These acids then go to work breaking down the metals and other materials of construction, adding soluble material to the chemical reaction. A number of other chemical reactions may take place, and the circulating refrigerant and oil carry the entire mix throughout the system where it can continue the process.

One authority on acids informs us that for every 18 degrees F an acid is heated, its activity level doubles.

Eventually, the motor winding insulation may be destroyed and the motor windings begin to pass electrical current between each other. As the motor begins to burn out, smoldering products from the burning motor are pumped throughout the system. Remember, the motor will be cooking and burning while the compressor is pumping these products through the system. Liquid refrigerant and oil are fairly good cleaning agents, so the piping where liquid refrigerant is located may remain fairly clean of the resulting debris. However, in the evaporator a distillation process is taking place, the refrigerant is changing from a liquid to a gas, so the debris becomes separated from the refrigerant and begins getting deposited in the evaporator and suction line. This is why the low side of a system that has experienced a compressor burnout is where the majority of the debris is located.

It is imperative that installation and service technicians prevent foreign materials, air, moisture, brazing flux, carbon created during brazing, and insulation powder from entering or remaining in a system. Good piping practice includes bleeding a small amount of dry nitrogen through the system while brazing. Pipe ends need to be sealed prior to sliding pipe insulation over the piping. A good 500-micron evacuation should be reached to remove air and moisture before charging with refrigerant. And, the addition of a properly sized filter-drier is important on both new systems as well as anytime a system is opened for service.

The filter-drier is designed to both remove any particulates that may circulate as well as collect and hold any moisture that may be present in the system. The use of a filter-drier containing a good desiccant has become even more important with the advent of R-410A systems, which utilize the highly hygroscopic synthetic polyolester oils.

The modern desiccant of choice is a material called zeolite. Zeolite has gained in popularity over the older desiccants such as activated alumina, silica gel, calcium chloride, and calcium oxide. Zeolite is a mineral that occurs in nature or can be manufactured. It is an inorganic tan or gray porous solid consisting of a structure of pores and tiny chambers capable of collecting and holding moisture through capillary action. Adsorption is the physical trait of capillary action whereby moisture is drawn into small pores much like a sponge or paper towel collects liquid spills.

There are hundreds of different zeolites, each with its own micro-sized shape, lattice structure, and size. Zeolites can be selected to collect and hold many different substances according to the molecular size and structure of the specific molecule one wishes to collect. The zeolite selected for use in a filter-drier is selected to adsorb moisture while allowing refrigerant to pass through. One example of a zeolite is a very light and porous volcanic rock. Zeolite filters are used as desiccants and filters for refrigerant, acids, specific chemicals, and to remove ammonia in fish tanks.

Zeolite desiccants are formed into a porous solid core, which is placed in the filter-drier container. Older loose-fill desiccants like silica gel occasionally broke down into particles or dust that sometimes left the filter-drier and circulated through the system, often creating a restriction especially on capillary tube systems. This was avoided by positioning the filter-drier vertically so pressure pulsations in the system would not shift the loose fill back and forth and physically break it down. Solid-core zeolite desiccant filter-driers may be installed in any position. Most solid-core desiccants are molded into a cylindrical block with a tapered axial hole down the center to allow for the uniform flow of the refrigerant through the entire bed of desiccant. This is why filter-driers are directional with the direction of flow indicated on the container. Installing the filter-drier in the wrong direction causes non-uniform refrigerant to desiccant contact and increases pressure drop. Bi-flow filter-driers are available for heat pump applications.

The capacity of a desiccant is temperature dependent. The colder the desiccant, the more moisture it can hold. Therefore, locating a filter-drier in a cooler location is an advantage. Removing a brazed filter-drier with a torch flame causes moisture to be driven out of the desiccant and into the system. Generally, it is better to cut the filter-drier out with a tubing cutter.

A suction line filter-drier with an excessive pressure drop across it should not be left in a system. An excessive pressure drop in the suction line reduces the volumetric efficiency of the compressor, thus reducing system operating capacity. Many suction line filter-driers have a pressure tap on the inlet end so the pressure on the inlet of the drier can be compared to the pressure at the suction service valve at the compressor. Still other suction line filter-driers have pressure taps on both the inlet and outlet.

Don’t allow a system to become an out of control chemistry set. Good piping practice, a nitrogen purge during brazing, a deep evacuation, and the proper installation and use of filter-driers containing modern and effective molecular sieve desiccants will prevent many system failures. Many compressor failures are blamed on the compressor when the actual cause was a system problem. That system problem may have been a chemical problem due to moisture.

Norm Christopherson is a technical writer, seminar presenter, and former HVACR instructor. He is currently seeking training opportunities. He can be contacted at [email protected].

Publication date: 09/08/2003